Question #1:
A nonmotor operated water heater rated 5.4 kW at 240-volt is connected with a piece of No. 6 copper THHN conductor. The appliance is not marked with a maximum OC device size. What is the maximum size of the overcurrent device permitted for this water heater?
(A) 50
(B) 40
(C) 35
(D) 30

Question #2:
Two small appliance circuits are connected as follows to a three-wire circuit. Line one to neutral has a 900 watt load connected to it. Line two to neutral has a 1300 watt load connected to it. With both loads turned on what is the wattage in the neutral?
(A) 2300
(B) 1300
(C) 900
(D) 400

Question #3:
The copper grounding electrode conductor required for a 1600-ampere service consisting of four sets of 750 kcmil THHN compact aluminum conductors in parallel is:
(A) 2/0       
(B) 3/0
(C) 250 kcmil
(D) 400 kcmil

Question #4:
What is the maximum size dual element fuse permitted to protect a 60 hp. 3-phase, 480-volt squirrel-cage motor that is connected with a piece of No. 3 copper THHN conductor?
(A)  80
(B) 125
(C) 150
(D) 175

Question #5:
A No. 14 THHN copper conductor is used within a motor starter as a control circuit conductor. What is maximum size circuit breaker permitted for the motor short-circuit, ground-fault protection that will protect this conductor?
(A) 15
(B) 20
(C) 45
(D) 100

Question #6:
What is the computed lighting load in amperes for a 208Y/120 feeder to supply an office area that is 125’ x 157’ and which has an unknown receptacle load?
(A) 307
(B) 245
(C) 413
(D) 293

Question #7:
A mobile home park has 35 mobile home lots connected to one service. Each mobile home has a calculated demand of 21,400 vA. What is the minimum size of the service conductors in amperes to service this park?
(A) 559
(B) 749
(C) 3,120
(D) 3,500

Question #8:
The minimum headroom of the working space in front of a 200-amp. panelboard in which the top "Main" circuit breaker is mounted 6ft 5 in. to the center of the breaker and the top of the panelboard is installed at a height of 6’11" in a new dwelling unit is _______ .
(A) No minimum
(B) 6ft. 5 in.
(C) 6 ft. 6 in.
(D) 6 ft. 11. in.

Question #9:
Which of the following is required for a receptacle installed under the eaves of a two-story dwelling to be used for fixed outdoor deicing and snow-melting equipment?
(A) Ground-fault circuit-interrupter protection for personnel must be provided.
(B) Ground-fault protection of equipment must be provided
(C) A dedicated 20-ampere circuit must be provided
(D) A dedicated 15-ampere circuit must be provided.

Question #10:
Branch-circuit conductors within 3 in. of a ballast within the ballast compartment shall have an insulation temperature rating not lower than _____ oC.
(A) 60
(
B)
75
(C) 90
(D) 105